FIRST FROST, FIRST WARNING: WHEN DID ANYONE LAST TEST YOUR HEATING SYSTEM WATER?

What your closed heating and cooling system is trying to tell you, and why October is the month to listen

The first frost has arrived, and for most buildings that means the heating is about to go from occasional to constant. The boilers fire, the radiators warm up, and everyone assumes the system will cope.

But the water inside a closed heating or cooling system is not new. It has been sitting in the same pipework for months, sometimes years, and nobody can see it. If it has not been tested recently, you do not actually know what condition it is in, and winter is the worst time to find out.

Why now, and not January

A system that has coped quietly through autumn is about to be asked to work flat out. If something has been building up inside it, the first cold snap is when it tends to show: cold spots, noisy pipework, a pump that is struggling, or a leak that was only waiting for the pressure.

Sampling the water in October gives you time to act. You can adjust the dosing, clean or flush the system, or fit filtration before the coldest weeks. Waiting until something fails means doing the same jobs in the middle of winter, with the heating off and people complaining.

Four problems that build up together

Closed systems tend to develop four problems side by side: corrosion, scale, biofouling and sedimentation. They are linked, so each one makes the others worse. Corrosion creates debris that settles. Debris gives bacteria somewhere to grow. Bacterial slime then speeds up corrosion again.

Without careful management, the result can be:

  • Energy wastage, because the system works harder to deliver the same heat
  • Poor system performance, with cold spots and unreliable circulation
  • Early replacement of plant and components
  • Leaks and water damage

The BSRIA BG50 guidance gives two practical points worth acting on. First, keep the water circulating so that solids do not settle and stagnation does not set in. BG50 recommends one hour a day. Second, every closed system should have a documented water treatment programme, so that someone is responsible for checking the water and recording what they find.

Three clues in your water treatment results

A closed system tells you when something is wrong, if you know where to look. When a water sample comes back, these three clues are worth reading closely.

  1. Treatment levels keep dropping. This can be a sign of water losses, from leaks or maintenance work. If it keeps happening, fitting a water meter helps you monitor how much fresh water is going into the system.
  2. Only the nitrite level is falling. This suggests nitrite reducing bacteria, which an NRB test can confirm. Some inhibitors, nitrite included, can actually promote corrosion once levels drop below the control limit.
  3. Glycol has dropped below 20%. At that level it can act as a food source for bacteria. The breakdown products can be acidic, which lowers the pH and raises the risk of corrosion. Keep it at 20% or above.

One more for systems that contain aluminium components: the pH must not exceed 8.5.

None of this is visible without sampling. BS8552 recommends sampling at least quarterly, and more often if water quality appears to be deteriorating, if works have been carried out or if the system has lost water. Samples should come from representative points, including the main circulation and the remote or terminal ends of the system, to give a true picture.

What can be living in your heating system

With Halloween close, it is a fitting time to mention three things that can live inside a closed system without anyone noticing. Pseudomonads are slime-forming bacteria that build biofilms, and those biofilms shelter other bacteria and act as a barrier that stops inhibitors from working. Sulphate reducing bacteria are one of the most frequent causes of microbially influenced corrosion. They thrive without oxygen under a biofilm and produce hydrogen sulphide, which corrodes metal. Nitrite reducing bacteria can strip out nitrite inhibitor quickly, making treatment less effective and corrosion faster.

You will not spot any of them from the boiler room. Three things help reduce the risk: dose with an appropriate biocide, limit the nutrients available to bacteria, and flush, clean and remove deadlegs.

Taking the solids out: side stream filtration

A newly installed filter pot on a closed heating system in a plant room, with insulated pipework around it
A newly installed filter pot. It removes solids from closed water systems to help maintain water quality.

Alongside testing and treatment, one of the simplest ways to protect a closed system is to remove the solids from the circulating water. Side stream filtration does exactly that. The unit in the photo is a newly installed filter pot, and units like it usually contain a magnet to capture magnetite, plus a physical filter to catch other contaminants, including bacteria.

It is an easy, safe and effective addition for most systems, and BG29/2020 strongly recommends it for systems holding more than 2,500 litres. The benefits include a lower risk of under-deposit corrosion and blockages, limited bacterial growth, and a longer system life with better efficiency. Like any filter, it needs to be checked and maintained regularly to keep working properly.

A simple checklist for this autumn

If you look after a building with a closed heating or cooling system, these are sensible questions to ask now:

  • When was the water last sampled, and are the results kept somewhere you can find them?
  • Is there a documented water treatment programme, and does someone own it?
  • Are treatment levels, nitrite and glycol where they should be?
  • Is the water being circulated regularly so that solids do not settle?
  • Does the system contain aluminium, and has the pH been checked?
  • Is there filtration in place, and when was it last checked?
  • Are there deadlegs that could be flushed, cleaned or removed?

Closed system sampling also sits comfortably alongside the rest of your water hygiene routine. If you already have a water hygiene inspection or a Legionella risk assessment in place, ask whether your heating and cooling systems are covered by the same review, and whether the results are kept in the same place. Our risk assessment page explains what a visit involves. We are based in Stockport and look after sites across Greater Manchester and the rest of the UK.

Your site’s own risk assessment and water treatment provider set the exact limits and testing schedule for your system. The figures in this article are general guidance and a starting point for that conversation.

Not sure when your system was last sampled?

Based in Stockport and working with sites across the UK, our water treatment team can look at your results, explain what they mean and point you in the right direction. Call 0161 430 5100 or email Technical@hydraclean.co.uk. You can also find out more about our water treatment and Legionella compliance services.

Get in touch today

Do you have a question about one of our services? Perhaps you would like to enroll on a training course? Get the ball rolling and fill out this form - we will get back to you as soon as possible.